| Model | MPR-E1 |
| Function | Phase Unbalance, Phase Reversal, Phase Failure, Under & Over Voltage, Under & Over Current, Under & Over Frequency Monitor and Control, Earth leakage protection |
| Rated supply voltage | 415V AC, 3 phase, 4 wire |
| Rated frequency | 50Hz ± 10% |
| Power consumption | 5VA / 1W |
| Input Current | Current Input (AR,AY,AB) Ib=5A |
| Voltage | ± 4V of display value |
| Current | ± 5% of Ib ± 1 digit (Ib=5A) |
| Frequency | ± 2% of FS ± 1 digit |
| Trip time | ± 1% of set delay ± 2 sec |
| Earth leakage current | ± 500mA of setting accuracy |
| Trip setting | Phase Unbalance : 1 to 20% (Adj.) |
| Under Voltage : 5 to 100V AC | |
| Over Voltage : 5 to 100V AC | |
| Over Current : 105% to 800% | |
| Under Current : 20%* to 95% | |
| Over Frequency : 2 to 5Hz | |
| Under Frequency : 2 to 5Hz | |
| Earth leakage Current sensitivity range : 1 to 8A | |
| Minimum sensing current* | 0.5A |
| Maximum setting current | 5A (Above 5A > Ext. CT can be used, CT setting max. 2500 / 5 Amp in steps of 5) |
| Trip time delay | 1 to 250 secs settable for UB, OV, UV, OC, UC |
| Earth leakage trip time delay | 5 sec Earth leakage |
| Phase failure trip time delay | < 5 sec |
| Phase reverse trip time delay | Instantaneous |
| Frequency trip time delay | Instantaneous |
| Recovery time | 2 sec Min |
| Power On delay | 10 sec Max. |
| Inrush current delay | 1 to 60sec Settable |
| Mode of Operation | Auto / Manual |
| Core Balance Current Transformer Type | Toriodal core |
| Control Output | 1 c/o rated for 10A @ 250V AC / 28V DC resistive load |
| Recovery time | 2 sec min |
| Ambient temperature | Operation: -100C to +550C, Storage: -250C to +800C |
| Humidity | Max. 85% RH @ 400C |
| Service life (under no load) | 106 operations minimum |
| Electrical life (under full load) | 105 operations minimum |
| Rated frequency of operation | 1800 ± 5% operations per hour max |
| Insulation resistance | >100M ohms @ 500V DC |
| Di-electrical strength | 1. 2.5KV AC, 50Hz for 1minute. (Between current carrying and non-current carrying parts). 2. 1.5KV AC, 50Hz for 1minute. (Between contacts and control circuit). 3. 750V AC, 50Hz for 1minute. (Between non-continuous contacts of the relay). |
| Electrical connection | Screw type terminals with self lifting clamps |
| Mode of operation | Manual / Auto |
| CBCT Size internal Diameter | Circular 75 / 100 mm |
| Dimension (over-all) | 96 x 96 x 97.5mm (W x H x D) |
| * Applicable for more than 2.5 Amps nominal current |


Instruction Manual —–1No. RC Filter —–1No.
Tools and Fasteners Kindly use star – type screw driver for tightening the screws.
NOTE: Installation should include a disconnecting device, like switch or circuit breaker, with clear ON/OFF markings, to turn-off the auxiliary
supply (control power).The disconnecting device should be within the reach of the equipment and the operator