| Model | M2-24 | M2-20 | M2-16 | M2-12 |
| Function | Programmable fault annunciator | |||
| Rated supply voltage | 85Vto 270V AC / DC | |||
| Stand by supply voltage | 12V DC ± 10% | |||
| Rated frequency | 50 / 60Hz ± 5% | |||
| Power Consumption | AC approx 30 VA /DC approx 20W | |||
| No. of windows | 24 windows | 20 windows | 16 windows | 12 windows |
| Fault input contacts | Selectable NO / NC type for each window | |||
| Window colour | Red | |||
| Control output (No. of relays) | 4 : Trip Relay (C, NC , NO), Alarm relay (C, NC , NO), AC fail relay (C, NO), Hooter Relay (C, NO) | |||
| Contact rating | 1 c/o rated for 5A @ 250V AC / 28V DC, resistive load | |||
| Test facility | Available (operational test) | |||
| Flash rate | Fast : 100 per minute Slow : 50 per minute | |||
| Standard sequence | Manual reset, Auto reset , Manual reset + Repeat Alarm, First in First out (FIFO) | |||
| Recovery time | 2 Sec minimum | |||
| Ambient temperature | Operation : -100C to +550C, Storage : -250C to +800C | |||
| Humidity | Max. 85% RH @ 400C | |||
| Service life (under no load) | 106 operations minimum | |||
| Electrical life (under full load) | 105 operations minimum | |||
| Insulation resistance | >100M ohms @ 500V DC | |||
| Di-electrical strength | 1. 2.5KV AC, 50Hz for 1minute. (Between current carrying and non-current carrying parts). 2. 1.5KV AC, 50Hz for 1minute. (Between contacts and control circuit). 3. 750V AC, 50Hz for 1minute. (Between non-continuous contacts of the relay).
| |||
| Electrical connection | Screw type terminals with self lifting clamps | |||
| Window size(W x H) | 28.0 mm2 | Big Window : 28.0mm X 63.0mm Small Window : 28.0 mm2 | 28.0mm X 63.0mm | |
| Dimension (over-all) | 291 x 186.5 x 79mm (WxHxD) | |||
| Enclosure (series) | ‘N’ series | |||


Tools and Fasteners:Kindly use star – type screw driver for tightening the screws.
NOTE: Specification Installation should include a disconnecting device, like switch or circuit breaker, with clear ON/OFF markings, to turn-off the auxiliary supply(control power).The disconnecting device should be within the reach of the equipment and the operator.